CONTROL SYSTEM        
Revision Y06-02 Service Manual - KN Series
d. STEP 3: AUTO LED WALK TEST. 
1)  All the LEDS will turn OFF. 
2)  All the LEDS will turn ON for 1 second one by one in the following sequence: 
 STAND-BY Ö OPERATE Ö TIMER Ö FILTER Ö COOL Ö HEAT. 
3) In PRX all the LEDS will turn ON for 1 second one by one in the following 
sequence : 18 °c Ö 20 °c Ö 22 °c Ö 24 °c Ö 26 °c Ö 28 °c Ö 30 °c Ö
High IFAN Ö Auto IFAN Ö Med IFAN Ö Low IFAN Ö STAND-BYÖ TIMER Ö
FILTER ÖCOOLÖ HEAT. 
e. STEP 4: 
AUTO REALY WALK TEST: 
All relays will energize one by one in the following sequence: 
COMPRESSOR Ö OUTDOOR FANÖR. V. Ö HEATER 1 Ö HEATER 2 Ö
INDOOR WATER PUMP Ö SWING or OUTDOOR WATER PUMP Ö INDOOR 
FAN: LOW Ö MID Ö HIGH. 
When the relay walk test is completed, the next test will start automatically. 
f. STEP 5: FREQUENCY TESTING: 
If the frequency measuring process fails the COOL LED will turn ON. In order to 
move to the next step, press ON/OFF button on the remote control. 
g. STEP 6: INPUT TEST. 
The test purpose is to check the analog real time indicators (thermistors, LEVEL 
and clock) according to the table below. 
LED Indicator  Condition for LED to be ON 
STBY LED 
Room
 thermistor z 25°c 
OPER LED 
Indoor coil thermistor z 25°c 
TIMER LED 
Outdoor coil thermistor z 25°c 
FILTER LED  Clock 
COOL LED  LEVEL 2&3 
HEAT LED  LEVEL 4 
h. STEP 7: TIMING RESET TEST (WATCH DOG). 
The test purpose is to verify that the CPU rise time after power failure is between 1 
to 3 sec, test results are indicated on the LEDS : STAND-BY,OPER, TIMER and 
FILTER turning ON one by one. 
The results of the test are coded as follows: 
Pass condition: 
1 sec - STAND-BY and OPER are turned ON 
2 sec - STAND-BY, OPER and TIMER are turned ON 