CONTROL SYSTEM
Revision Y06-02Service Manual - KN Series
11.13 Forced Operation (Excluding PRX & PXD Models) 
a.  Forced operation allows units to start, stop and operate in cooling or heating in 
preset temp. according to the following table: 
Forced
Operation Mode 
Pre-set Temp for : 
MBX, P2000, PX Models 
Pre-set Temp for : 
FCD, RWK ,ELD, ECC, WAX, WNX, WMN Models 
Cooling 20 ºC  22 ºC 
Heating 25 ºC  28 ºC 
NOTES
1.  While under the forced operation, the temperature compensation 
schedule is disabled. 
2. The forced operation is activated when the mode button on the 
Display Board is used to switch the unit to COOL or HEAT mode. 
3.  The IFAN is always set to Autofan Speed in forced operation. 
Temp:  Set – desired temperature selected 
Fan:  Any 
Timer: Interact with Sleep Timer 
I-FEEL: ON or OFF 
The Sleep mode is activated by using the SLEEP button on the R/C. In Sleep Mode, 
the unit will automatically adjust the SPT to turn up/down the room temperature (RT) 
gradually to provide maximum comfort for the sleeping user. 
Sleep is treated as TIMER function. Therefore, the TIMER LED is activated si
milar to 
TIMER function. 