CONTROL SYSTEM        
Revision Y06-02 Service Manual - KN Series
11.12.3 Heating Mode Protections 
a.  Outdoor Coil Deicing (excluding RH Group) 
Mode: HEATING, AUTO (at heating) 
Temp:  Selected desired temperature 
Fan:  Any 
Timer:  Any 
I-FEEL:  Any 
Control function
To protect the outdoor coil from ice formation by controlling COMP & RV operation. 
1) Deicer Activation Algorithm 
a)  Static deicer threshold is -5°C 
b) Dynamic deicer threshold changes of 3°C in 3 minutes in the OCT 
temperature
c) In first COMP activation (after SB or OFF), if  OCT < 0°C, m in time to first 
deicer is 10 min else 40 min. 
d)  In a case of reading 3 successive OCT values below –10°C and 
previously 3 successive OCT values of 43°C (4.7 K) , the unit will activate 
deicing procedure. 