Service manual
11-18
CONTROL SYSTEM        
Revision Y06-02 Service Manual - KN Series
11.10 Automatic Cooling or Heating 
11.10.1 Automatic Cooling or Heating - General 
The AUTO Mode is for models with compressor and the WVL-RH only. The WVL-ST, 
RC and SH units do not work in AUTO Mode. 
a. Mode Definition 
Mode:  AUTO 
Temp:  Selected desired temperature 
Fan:  Any 
Timer:  Any 
I-FEEL: ON or OFF 
b. Switching-temperature between Cooling and Heating is SPT r 3
O
C.
c. When the AUTO Mode is started with SPT +/-0
 O
C, the unit will not select Auto 
Heat or Auto Cool mode immediately. Instead, the unit will be in a temporary FAN 
Mode with IFAN operating at low speed. The proper Auto Heat mode or Auto Cool 
will be started whenever the RT reaches SPT-1
O
C or SPT+1
O
C respectively. 
d.  For RC & SH units, Mode change between Auto Heat & Auto Cool Modes is 
possible only after the COMP has been OFF during the last T minutes. 
Mode Change Time, T 
Auto Cool to Auto Heat  3 min 
Auto Heat to Auto Cool  4 min 
e.  For RH and WVL-RH units, Mode change between Auto Heat & Auto Cool Modes 
is possible after the COMP/HEs have been OFF during the last T minutes. 
Mode Change Time, T 
Auto Cool to Auto Heat  COMP off for 3 min 
Auto Heat to Auto Cool  HEs off for 3 min 
f.  When unit is changed form Cool/Dry Mode to Auto Mode, the unit will continue to 
operate in (Auto) Cool Mode until the conditions for switching from Auto Cool to 
Auto Heat are satisfied. 
Similarly, when unit is changed fro
m Heat Mode to Auto Mode, the unit will 
continue to operate in (Auto) Heat Mode until the conditions for switching from 
Auto Heat to Auto Cool are satisfied. 