Service manual
14-5
OPTIONAL ACCESSORIES
Revision Y06-02
Service Manual - KN Series
2
Fig.4
●  Connect capillary E to T-valve. 
 Use Copper sealing gasket between the flare nut 
and the connection to T-valve.
Note:
● Installing the Copper sealing gasket is mandatory 
in order to avoid refrigerant leak. 
Cooper sealing 
gasket
Fig.5
Fig.6
E
T-valve
D
Flare nut
TB2 
TB5 
TB4 
TB1 
Electrical connections for 3PH units:
●  Disconnect the wire from point “6”  on main ter-
minal PCB Typhoon and isolate it with isolation 
tape.
●  Disconnect the JP1 and JP2 wires from tabs TB1; 
TB8; TB9 on PCB Typhoon.
●  Connect Red Wire from Fan Speed Controller to 
tab “TB8” on PCB Typhoon.
●  Connect Green Wire from Fan Speed Controller 
to Tab “TB1” on PCB Typhoon.
●  Connect Y/Green wire from Fan Speed Controller 
to ground screw on units partition.
●  Return  “JP1” wire, previously disconnected, to 
Electrical connections for 1PH units:
●  Disconnect the wire from point “6” on main ter-
minal outdoor PCB Typhoon and isolate it with 
isolation tape.
●  Disconnect the JP1 and JP2 wires from tabs TB2; 
TB4; TB5 on PCB Typhoon. 
  Connect the Red Wire from Fan Speed Controller 
to tab “TB4” on PCB Typhoon.
●  Connect Green Wire from Fan Speed Controller 
to tab “TB2” on PCB Typhoon.
●  Connect Y/Green wire from Fan Speed Controller 
to ground screw on units partition.
●  Return  “JP1” wire, previously disconnected, to 
tab “TB2”. 
Ground screw 
TB2 
TB5 
TB4 
Ground screw 
Fig.5
Fig.4
Fig.6
TB8 
TB9 
TB1 
TB8 
TB9 