Service manual
2-5
PRODUCT DATA SHEET
Revision Y06-02Service Manual - KN Series
2.5  KN 36 / OU10-36 R410A 
Model Indoor Unit  KN 36 
Model Outdoor Unit  OU10-36 R410A 
Installation method  CASSETE 
Characteristics Units Cooling Heating 
Btu/hr 34,500  34,500 
Capacity (1) 
kW 10.10  10.10 
Power input (1)  kW  3.48  3.60 
COP (1)  W/W  2.90  2.80 
Energy efficiency class      C    D 
Power supply  V/ Ph /Hz 230/50/1 
Rated current  A  16.2  16.3 
Starting current  A  92 
Circuit breaker rating  A  25 
Fan type & quantity    Centrifugal & 1 
Fan speeds  H/ M/ L  RPM  580  540  500 
Air flow (2)  H/ M/ L  m³/hr  1220  1125  1025 
External static pressure  Min-Max Pa  N/A 
Sound power level (3)  H/ M/ L  dB(A)  53  51  49 
Sound pressure level (4)  H/ M/ L  dB(A)  46  44  42 
Moisture removal  L/hr  4.1 
Condensate drain tube I.D  mm  32 
Dimensions (Unit / Frame)  W/ H / D  mm  840 / 950  840 / 950  300 / 46 
Weight kg 48 
Package dimensions 
(Unit / Frame) 
W/ H / D  mm  1011 / 1013  931/ 1013  400 / 145 
Packaged weight  kg  52 
Units / Frames per pallet  Units  5 / 15 
INDOOR 
Stacking height Units / Frames  Units  5 / 15 
Refrigerant control    Capillary tube 
Compressor type, model    Scroll 
Fan type & quantity    Axial & 2 
Fan speeds  H / L  RPM  1150   
Air flow  H / L  m³/hr  4150   
Sound power level  H / L  dB(A) 70.4   
Sound pressure level (4)  H / L  dB(A) 61.1   
Dimensions  W/ H / D  mm  900  970  340 
Weight kg 87 
Package dimensions  W/ H / D  mm  985  1020  435 
Packaged weight  kg  91 
Units per pallet  Units  6 
Stacking height  Units  2 
Refrigerant type    R 410A 
Refrigerant charges distance  kg/m  2.55/15 
Additional charge per 1 meter  g/m  30 
Liquid line  In.  3/8 
Suction line  In.  3/4 
Max. tubing length  m.  50 
OUTDOOR 
Connections 
between 
units 
Max. height 
difference 
m. 25 
Operation control type    LCD Remote Control 
Heating elements  kW  3.0 
Others    Crankcase heater (50W), 3 Phase Protector
(1) Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units). 
(2) Airflow in ducted units; at nominal external static pressure. 
(3) Sound power in ducted units is measured at air discharge. 
(4) Sound pressure level measured at 1-meter distance from unit.
Crankcase heater (50W)
CONTENT