Service manual
2-4
PRODUCT DATA SHEET
Revision Y06-02 Service Manual - KN Series
Model Indoor Unit  KN-30
Model Outdoor Unit  OU830T 
Installation Method of Pipe  Flared 
Characteristics Units Cooling Only Cooling Heating 
Btu/hr 28,300 28,300 30,500 
Capacity 
(1)
kW 8.30 8.30 8.94  
Power input 
(1)
 kW 2.86 2.86 2.79  
EER (Cooling) or COP(Heating) 
(1)
  W/W  2.9  2.9  3.20 
Energy efficiency class     
C C 
D
Power supply  V/Ph/Hz  400V/3PH/50Hz 
Rated current  A  3 x 5.2  3 x 5.2  3 x 5.2 
Starting current  A  35 
Circuit breaker rating  A  3 x 16 
Fan type & quantity      Centrifugal x 1 
Fan speeds  H/M/L  RPM  740/700/620 
Air flow 
(2)
 H/M/L m3/hr 1200/1120/985 
External static pressure  Min-Max  Pa  N/A 
Sound power level 
(3)
 H/M/L dB(A)  61/59/56 
Sound pressure level
(4)
 H/M/L dB(A)  52/50/47 
Moisture removal  l/hr  3.2 
Condensate drain tube I.D  mm  32 
Dimensions  WxHxD  mm  840x230x840 (Unit) / 950x46x950 (Frame) 
Weight  kg  36 (unit) / 6 (Frame) 
Package dimensions  WxHxD  mm  1011x333x931 (Unit) / 1013x145x1013(Frame) 
Packaged weight  kg  40 (unit) / 7 (Frame) 
Units per pallet  units  5(Unit) / 15(Frame) 
INDOOR
Stacking height  units  5 Levels (unit) / 15 Levels (Frame) 
Refrigerant control       Capillary 
Compressor type, model      Rotary, Mitsubishi NN33YCAMT 
Fan type & quantity      Propeller(direct) x 1 
Fan speeds  H/L  RPM  850 
Air flow  H/L  m3/hr  3150 
Sound power level  H/L  dB(A)  69 
Sound pressure level
(4)
 H/L dB(A)  59 
Dimensions WxHxD mm 900x860x340 
Weight kg 78 
Package dimensions  WxHxD  mm  985x907x435 
Packaged weight  kg  82 
Units per pallet  Units  6 
Stacking height  units  2 Levels 
Refrigerant type      R410A 
Refrigerant chargless distance  kg/m  2.42kg/15m 
Additional charge per 1 meter  g/m  30 
Liquid line  In.(mm)  3/8"(9.53) 
Suction line  In.(mm)  5/8"(15.88) 
Max .tubing length  m.  Max.30 
OUTDOOR 
Connections between units 
Max .height 
difference
m. Max.15 
Operation control type      Remote control 
Heating elements  kW     
Others  Crankcase heater (50W),3PH Protector 
(1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN 14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
2.4  KN 30 / OU8-30T R410A
CONTENT