SAF Fixed RPM Series Indoor Units SAF024 SAF045 Outdoor Units OU7-24Z OU10-47T GC 45 REFRIGERANT COOLING ONLY R22 HEAT PUMP R410A SM SAFRPM 1-A.
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters. Dates of issue for original and changed pages are: Original ....... 0 ........ March 2009 Total number of pages in this publication is 53 consisting of the following: Page No. Revision No. # Title .......................
TABLE OF CONTENTS Table of Contents 1. INTRODUCTION ...................................................................................................1-1 2. PRODUCT DATA SHEET ......................................................................................2-1 3. RATING CONDITIONS ..........................................................................................3-1 4. OUTLINE DIMENSIONS .......................................................................................4-1 5.
INTRODUCTION 1. INTRODUCTION 1.1 General The floor-standing air conditioner of SAF fixed RPM series has some strongpoint, such as modern outlook, excellent quality, amazing price. It comprise RC, RH, models, as follows: • SAF024 R410A • SAF045 R410A • SAF045 R22 1.2 Main Features The SAF Fixed RPM series benefits from the most advanced technological innovations, namely: • LCD display • Ionizer as an option • Auxiliary PTC heater as an option.
INTRODUCTION 1.6 Tubing Connections Flare type interconnecting tubing to be produced on site. For further details please refer to the Owner’s Manual. 1.7 Accessories Remote Control 1.8 Inbox Documentation Each unit is supplied with its Owner’s Manual. 1.9 Matching Table Indoor Unit SAF024 SAF045 Outdoor Unit OU7-24Z OU10-47T GC 45 R22 SM SAFRPM 1-A.
PRODUCT DATA SHEET 2. PRODUCT DATA SHEET 2.
PRODUCT DATA SHEET 2.2 SAF045 / OU10-47T R410A Model Indoor Unit Model Outdoor Unit Installation method Characteristics Capacity (1) OUTDOOR INDOOR Power input (1) COP (1) Energy efficiency class Power supply Rated current Starting current Circuit breaker rating Fan type & quantity Fan speeds H/ M/ L Air flow (2) H/ M/ L External static pressure Min-Max H/ M/ L Sound power level (3) H/ M/ L Sound pressure level (4) Moisture removal Condensate drain tube I.
PRODUCT DATA SHEET 2.
RATING CONDITIONS 3. RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: 27oC DB 19oC WB Outdoor: 35 oC DB Heating: Indoor: 20oC DB Outdoor: 7oC DB 6oC WB 3.
OUTLINE DIMENSIONS 4. OUTLINE DIMENSIONS 4.1 Indoor Unit: SAF024, SAF045 C Model SAF024 SAF045 A 485 mm 545 mm B 300 mm 420 mm C 1730 mm 1780 mm A B 4.2 Outdoor Unit: OU7-24Z R410A SM SAFRPM 1-A.
OUTLINE DIMENSIONS 4.3 Outdoor Unit: OU10-47T R410A 4.4 Outdoor Unit: GC 45 R22 950 187.5 81 80.8 378 340 112.5 65.4 572 1270 SM SAFRPM 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5. PERFORMANCE DATA 5.1 SAF024 / OU7-24 Z R410A 5.1.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OD Coil(oC) 15 20 (1) (1) 25 30 35 40 46 ENTERING AIR WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 7.01 4.88 7.26 5.09 7.43 5.28 7.61 5.42 7.72 5.52 1.68 1.68 1.69 1.69 1.70 6.78 4.78 7.15 5.04 7.37 5.25 7.55 5.40 7.71 5.50 1.
PERFORMANCE DATA & PRESSURE CURVES 5.1.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL(Oc) 15 20 25 ENTERING WB OD COIL(oC) TH Pl TH Pl TH Pl -10 3.86 1.83 3.71 1.95 3.56 2.05 -7 4.15 1.88 4.01 1.98 3.86 2.09 -2 4.41 1.90 4.26 2.02 4.12 2.13 2 5.37 1.99 5.15 2.12 4.92 2.24 6 7.57 2.14 7.35 2.29 7.09 2.43 10 8.23 2.26 8.01 2.42 7.79 2.58 15 8.89 2.36 8.67 2.54 8.45 2.70 20 9.37 2.43 9.15 2.
PERFORMANCE DATA & PRESSURE CURVES 5.2 SAF045 / OU10-47T R410A 5.2.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB OD Coil(oC) 15 20 (1) (1) 25 30 35 40 46 ENTERING AIR WB/DB ID Coil(oC) 15/21 17/24 19/27 21/29 23/32 Data TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI TC SC PI 12.96 9.22 13.43 9.61 13.74 9.98 14.07 10.23 14.28 10.42 3.11 3.11 3.12 3.12 3.14 12.54 9.03 13.22 9.52 13.64 9.92 13.96 10.21 14.26 10.39 3.37 3.38 3.
PERFORMANCE DATA & PRESSURE CURVES 5.2.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL(Oc) 15 20 25 ENTERING WB OD COIL(oC) TH Pl TH Pl TH Pl -10 7.25 3.50 6.97 3.72 6.69 3.91 -7 7.80 3.58 7.52 3.78 7.25 3.99 -2 8.28 3.63 8.00 3.85 7.73 4.06 2 10.07 3.80 9.66 4.04 9.25 4.28 6 14.21 4.09 13.80 4.37 13.32 4.64 10 15.46 4.31 15.04 4.61 14.63 4.93 15 16.70 4.50 16.28 4.85 15.87 5.16 20 17.60 4.
PERFORMANCE DATA & PRESSURE CURVES 5.3 SAF045 / GC 45 R22 5.3.1 Cooling Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. Entering Air DB OD Coil (oC) 15 (1) (1) 20 25 30 35 40 46 Data Entering Air WB/DB ID Coil (oC) 15/21 17/24 19/27 21/29 23/32 TC 13.49 13.97 14.30 14.64 14.86 SC 9.55 9.96 10.34 10.60 10.80 PI 3.23 3.24 3.25 3.25 3.27 TC 13.05 13.76 14.19 14.53 14.84 SC 9.36 9.87 10.28 10.57 10.77 PI 3.51 3.52 3.53 3.55 3.56 TC 12.
PERFORMANCE DATA & PRESSURE CURVES 5.3.2 Heating Mode at 7.5m Tubing Connection. 230V : Indoor Fan at High Speed. ENTERING AIR DB ID COIL)O C) 15 20 25 ENTERING WB OD COIL)o C) TH Pl TH Pl TH Pl -10 8.09 4.10 7.78 4.36 7.47 4.58 -7 8.70 4.20 8.39 4.43 8.09 4.67 -2 9.24 4.25 8.93 4.51 8.62 4.76 2 11.24 4.45 10.78 4.74 10.32 5.02 6 15.86 4.79 15.40 5.12 14.86 5.44 10 17.25 5.05 16.79 5.40 16.32 5.78 15 18.63 5.27 18.17 5.68 17.71 6.04 20 19.64 5.
PERFORMANCE DATA & PRESSURE CURVES 5.4 Pressure Curves: SAF024 / OU7-24 Z R410A 5.4.1 Cooling. Discharge Pressure (Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 15 :% '% |& :% '% |& :% '% |& :% '% |& :% '% |& 20 25 30 35 Outdoor Temp.(DB oC ) 40 46 40 46 Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 11.0 10.0 :% '% |& :% '% |& :% '% |& :% '% |& :% '% |& 9.0 8.0 7.0 6.
PERFORMANCE DATA & PRESSURE CURVES 5.4.2 Heating. Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 '% |& '% |& '% |& -10 -5 0 5 10 Outdoor Temp.( WB oC ) 15 20 Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 11.0 10.0 9.0 8.0 7.0 '% |& '% |& '% |& 6.0 5.0 4.0 3.0 -10 -5 0 5 10 Outdoor Temp.( WB oC ) 15 20 SM SAFRPM 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.5 Pressure Curves: SAF045 / OU10-47T R410A 5.5.1 Cooling. Discharge Pressure (Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 15 :% '% |& :% '% |& :% '% |& :% '% |& :% '% |& 20 25 30 35 Outdoor Temp.(DB oC ) 40 46 40 46 Suction Pressure VS.Outdoor Temp Suction Pressure (Bar[g]) 12.0 11.0 10.0 :% '% |& :% '% |& :% '% |& :% '% |& :% '% |& 9.0 8.0 7.0 6.
PERFORMANCE DATA & PRESSURE CURVES 5.5.2 Heating. Discharge Pressure(Bar[g]) Discharge Pressure VS.Outdoor Temp 40 38 36 34 32 30 28 26 24 22 20 18 16 '% |& '% |& '% |& -10 -5 0 5 10 Outdoor Temp.( WB oC ) 15 20 Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 11.0 10.0 9.0 8.0 7.0 '% |& '% |& '% |& 6.0 5.0 4.0 3.0 -10 -5 0 5 10 Outdoor Temp.( WB oC ) 15 20 SM SAFRPM 1-A.
PERFORMANCE DATA & PRESSURE CURVES 5.6 Pressure Curves: SAF045 / GC 45 R22 5.6.1 Cooling. Discharge Pressure VS.Outdoor Temp Discharge Pressure (Bar[g]) 30 28 26 24 22 :% '% |& :% '% |& :% '% |& :% '% |& :% '% |& 20 18 16 14 12 10 8 15 20 25 30 35 40 46 40 46 Outdoor Temp.(DB oC ) Suction Pressure (Bar[g]) Suction Pressure VS.Outdoor Temp 4.5 15 20 :% '% |& :% '% |& :% '% |& :% '% |& :% '% |& 25 30 35 3.5 2.
PERFORMANCE DATA & PRESSURE CURVES 5.6.2 Heating. Discharge Pressure VS.Outdoor Temp Discharge Pressure(Bar[g]) 24 22 20 18 '% |& '% |& '% |& 16 14 -10 -5 12 0 5 10 15 20 Outdoor Temp.( WB oC ) Suction Pressure VS.Outdoor Temp Suction Pressure(Bar[g]) 6.0 5.0 4.0 3.0 -10 -5 0 5 10 15 '% |& '% |& '% |&20 2.0 Outdoor Temp.( WB oC ) SM SAFRPM 1-A.
SOUND LEVEL CHARACTERISTICS 6. SOUND LEVEL CHARACTERISTICS 6.1 Sound Pressure Level Figure 1 6.2 Sound Pressure Level Spectrum (Measured as Figure 1) SAF045 -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.
SOUND LEVEL CHARACTERISTICS 6.3 Outdoor units Unit 1m Mic. Ground Figure 2 6.4 Sound Pressure Level Spectrum (Measured as Figure 2) OU7-24 Z Heating -70NC -60NC -50NC -40NC -30NC APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE -20NC MICRO BAR0.002 dB re , OCTAVE BAND SOUND PRESSURE LEVEL MICRO BAR0.
WIRING DIAGRAMS 7. WIRING DIAGRAMS 7.1 Indoor Units: SAF024, SAF045 SM SAFRPM 1-A.
WIRING DIAGRAMS 7.2 Indoor Unit: OU7-24 Z R410A SM SAFRPM 1-A.
WIRING DIAGRAMS 7.3 Indoor Unit: OU10-47T R410A SM SAFRPM 1-A.
WIRING DIAGRAMS 7.4 Outdoor Unit: GC 45 R22 SM SAFRPM 1-A.
WIRING DIAGRAMS 7.5 Connections between indoor unit and outdoor unit SAF 24 SAF 45 Note: 1. ─ ─ ─ ─ Connection only for heat pump model 2. * Option, Power supply from outdoor or indoor unit SM SAFRPM 1-A.
ELECTRICAL DATA 8. ELECTRICAL DATA 8.1 SAF024, SAF045 Note: Power wiring cord should comply with local laws and electrical regulations requirementsl. SM SAFRPM 1-A.
REFRIGERATION DIAGRAMS 9. REFRIGERATION DIAGRAMS 9.
REGRIGERATION DIAGRAMS 9.2 SAF045 / OU10-47T R410A SM SAFRPM 1-A.
REFRIGERATION DIAGRAMS 9.3 SAF045 / GC 45 R22 SM SAFRPM 1-A.
TUBING CONNECTIONS 10. TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” 11-13 13-20 11-13 40-45 13-20 11-13 60-65 18-25 11-13 70-75 18-25 11-13 80-85 40-50 11-13 TORQUE (Nm) Flare Nuts Valve Cap Service Port Cap 1. 2. 3. 4. 5. 6. 7. 8.
CONTROL SYSTEM 11. CONTROL SYSTEM 11.1 SAFETY CONTROL 11.1.1 Time delay safety control a. 3 minutes delay for compressor—the compressor is ceased for 3 minutes to balance the pressure in the refrigenration cycle in order to protect the compressor. b. 2 minutes delay for 4-way valve—The 4-way valve is ceased for 2 minutes to prevent the refrigenrant-gas abnormal noise when the HEATING operation is OFF or switch to the other operation mode. 11.1.
CONTROL SYSTEM 11.4 “DRY” Mode Operation 1.4.1 The system for DRY operation used the same refrigerant circle as the cooling circle. 12.4.2 When the system operates in DRY mode, at first it operates in cooling mode at 16OC or 18OC for 3 minutes. And then, the system operates in cooling mode with low speed that regards the temperature of the room temperature sensor reads decrease 2OC as the set temperature.
CONTROL SYSTEM 11.5.5 Defrost Defrosting of the outdoor heat exchange is controlled by the microprocessor with detection by the indoor pipe temperature sensor. Defrost control type is according to the JC on the PCB whether is connected. 1. When the JC is connect on the PCB When one of the conditions of A, Band C is satisfy, the defrosting operation stars. In the condition A, it must satisfy the condition a),b) and c) then into defrosting operation.
CONTROL SYSTEM B. After the compressor cumulative operation time exceeds 120 minutes and the temperature of the IPT is less then 35OC for 2 minutes. When the defrosting operation time on this condition exceeds 8minutes, it will terminate. C. After the compressor operation continuously for 20 minutes and the IPT is less than 23OC or from the last time of defrosting operation is 50 minutes or more intervals. When the defrosting operation time on this condition exceeds 10 minutes, it will terminal. 2.
CONTROL SYSTEM 11.8 “SLEEP” mode When the SLEEP button is pressed, the SLEEP mode is selected as following: 1. The indoor fan speed is set at the low speed, the power lamp and the sleep lamp is on, the temperature off after 5 minutes. 2. When selecting COOLING/DRY operation with SLEEP mode, the set temperature will be raised by 1OC 1 hour later and 2OC 2 hour later. 3. When selecting HEATING operation with SLEEP mode, the set temperature will be dropped by 1OC 1 hour later and 2OC 2 hour later. 4.
CONTROL SYSTEM 11.11.2 Positioning The vane is once pressed to the cane stopper below to confirm the standard position and then set to the desired angle. The positioning is decided as follows: a. When the ON/OFF button is pressed. b. When the vane control is change from AUTO to MANUAL. c. When the SWING is finished. d. When the test run starts. e. When the power supply turns ON. 11.11.3 The auto vane changes as follows by pressing the VANE CONTROL button. 11.11.
CONTROL SYSTEM The thermostat is ON and timer is reset to normal. After 30 minutes of test run operation the system shifts to AUTO COOLING/Heating mode, and the indoor fan runs in automatic speed. The operation continues unit the EMERGENCY operation switch is pressed or a button on the remote controller is pressed, the normal operation will start. Note: Do not press the EMERGEMCY operation switch during normal operation. 11.14 AUTO RESTART Function (Option) 11.14.
CONTROL SYSTEM 11.16.4 Display of the control In the display board the lamp from left is the POWER lamp (Red), the SLEEP lamp (Yellow), the TIMER lamp (Yellow), the RUN lamp (Green) 11.16.5 When gives the control electric, the buzzer voices a long for 0.3 second per cycle. 12.17 Control logic for the heater The control logic for the heater is as follows: Condition to Cut in: If all following conditions are satisfied, the heater can operate: 1. The running time for the compressor exceeds 10 seconds. 2.
TROUBLESHOOTING 12. TROUBLESHOOTING Trouble Analysis If the protector trips or fuse is blown. ? Does not run If the leakage breaker trips. If the plug loosened. Sometimes it stops working to protect the appliance.
EXPLODED VIEWS & SPARE PARTS LISTS 13. EXPLODED VIEWS & SPARE PARTS LISTS 13.1 Indoor Unit: SAF024 SM SAFRPM 1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.2 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.3 Indoor Unit: SAF045 SM SAFRPM 1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.4 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.5 Outdoor Unit: OU7-24 Z *Optional 20 18 44 17 24 19a SM SAFRPM 1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.6 No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.7 Outdoor Unit: OU10-47T SM SAFRPM 1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.8 Outdoor Unit: OU10-47T SP No.
EXPLODED VIEWS & SPARE PARTS LISTS 13.9 Outdoor Unit: GC 45 R22 SM SAFRPM 1-A.
EXPLODED VIEWS & SPARE PARTS LISTS 13.10 Outdoor Unit: GC 45 R22 No. Part No. Description Quantity 1 4517832 TOP COVER PAINT ASSY 1 2 4517144 FAN COVER PP+UV/GRILL A 2 3 4520871 BASE PLATE PAINT ASSY. 1 4 4522238 LEFT FRONT PANEL PAINTED ASSY.
APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► INSTALLATION & OPERATION MANUAL SAF024 ► INSTALLATION & OPERATION MANUAL SAF045 SM SAFRPM 1-A.