Service manual
11-15
TROUBLESHOOTING
SM KN DCI 2-E.2 GB
No Fault Name Probable Cause Corrective Action
18 No communication A No signals in line A Check communication
19
Compressor- Ilegal 
Speed
Exceeds speed low limit See # 13
20
System Configuration 
Changed
Communication lines changed 
from last operation
No problem just an 
announcement
21
System Configuration 
Problem
Miss-match between the IDUs 
connected to port A,B,C or D, 
or the total capacity code of 
IDUs is higher than the ODU 
maximum capacity code
Change configuration if 
needed.
22
Heat sink Over 
Heating Fault/
Protection
Compressor stopped due to 
heatsink protection
Check that the airflow around 
the ODU is free and the fan is 
running free. Check fan motor 
(0)
23 Deicing Protection During deicing procedure No action required
24
Compressor Over 
Heating Protection
Compressor stopped due to 
over heat protection
Check if gas is missing in the 
system
25
System over power 
Protection
Compressor stopped due to 
over power protection
No action required 
26 Bad EEPROM EEPROM not operating
Power reset. (Replace 
Controller just in case you need 
EEPROM). 
27 Not Configured Cannot start the control
Power reset. Replace 
Controller if didn’t help
28 Bad Communication Bad communication lines See # 18-21