Service manual
3-1
RATING CONDITIONS                                 
Revision Y05-01Service Manual - KN Series
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) 
and EN 14511. 
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
 o
C DB
Heating:
Indoor: 20
o
C DB 
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating Limits
Indoor Outdoor
Cooling
Upper limit 32
o
C DB 23
o
C WB 46
o
C DB
Lower limit 21
o
C DB 15
o
C WB 10
o
C DB
Heating
Upper limit 27
o
C DB 24
o
C DB 18
o
C WB
Lower limit 10
o
C DB -9
o
C DB -16
o
C WB
Voltage
1PH 198 – 264 V
3PH 360 - 440 V
CONTENT