Operating Instructions and Installation Instructions

ULTRAMAX PB 65 - 120
53 L290 ©MHS Boilers 13/12/2010
Display
or
QAA73 #
Function / Description
Range
Default Values
65
85
100
120
H700
1st Historical Fault Number of
Occurrences.
H701
1st Historical Fault Operating Phase.
H702
1st Historical Fault Operating Error
Code
H703
2nd Historical Fault Number of
Occurrences.
H704
2nd Historical Fault Operating Phase.
H705
2nd Historical Fault Operating Error
Code
H706
3rd Historical Fault Number of
Occurrences.
H707
3rd Historical Fault Operating Phase.
H708
3rd Historical Fault Operating Error
Code
H709
4th Historical Fault Number of
Occurrences.
H710
4th Historical Fault Operating Phase.
H712
5th Historical Fault Number of
Occurrences.
H713
5th Historical Fault Operating Phase.
H714
5th Historical Fault Operating Error
Code
H715
Current Historical Fault Number of
Occurrences
H716
Current Historical Fault Operating
Phase.
H717
Current Historical Fault Operating Error
Code
H718
Hours run burner
0 ... 131070 hrs
0
0
0
0
H719
Hours run heating mode
0 ... 131070 hrs
0
0
0
0
H720
Hours run DHW heating
0 ... 131070 hrs
0
0
0
0
H721
Hours run zone
0 ... 131070 hrs
0
0
0
0
H722
Start counter
0 ... 327675
0
0
0
0
H723
Mean boiler output
-
H724
Selection of summer / winter operating
modes
0 ... 255
1
1
1
1
H725
SW version of LMU for presentation on
the OT parameter setting level
-
H726
Maintenance code contains
enumeration value of maintenance
alarm (precise cause)
0 ... 255
0
0
0
0
H727
Diagnostic Code
H728
1st Historical Fault ALBATROS Error
Code