Operation Manual

Table Of Contents
11
Error reports / Maintenance
Error reports
An error has been detected in the
facility, when this symbol is shown.
Detailed information is available by
pushing the information button.
Error reports / Maintenance
In exceptional cases, one of the
following symbols will be displayed in
the default display:
Maintenance or special mode
When this symbol is displayed, then
a maintenance report is displayed
or the facility is in special mode.
Detailed information is available by
pushing the information button.
Text3 Text4
30:Vorlauffühler 1
0
4 8 12 16 20 24
AUT O
Fehler
Text3 Text4
3:Wartungsintervall
0
4 8 12 16 20 24
AUT O
Wart ung
Display lists
Error code
Maintenance code
Error code Description of the error
0 No entry in Albatros code
10 Weather sensor defect
20 Boiler temperature 1 - sensor defect
32 Inlet temperature 2 - sensor defect
40 Outlet temperature 1 - sensor defect
50 DHW temperature sensor / thermostat 1 defect
52 DHW temperature sensor / thermostat 2 defect
61 Room unit 1 defect
62 Room unit 1 wrong type
78 Water pressure sensor defect
81 LPB short-circuit or no communication
82 LPB address collision
92 Equipment electronics error
105 Maintenance report
110 Safety temperature limiter defect deactivation
117 Water pressure too high
118 Water pressure too low
119 Water pressure switch triggered
121 Inlet temperature heating circuit 1 not reached
122 Inlet temperature heating circuit 2 not reached
128 Flame failure during operations
132 Safety deactivation of gas pressure switch, due to waste gas thermostat
or gas pressure monitor
133 Safety time limit for ame combustion exceeded
151 LMS 14… internal error
152 Parameterization error
153 Facility manually locked
154 Plausibility criteria infringed
160 RPM threshold of blower not reached
161 Maximum blower RPM exceeded
180 Chimney sweep function is active
181 Control unit stop function is active
182 Sitherm Pro electrode drift test is active
184 Modem function is active
185 Attic drying function is active
Maintenance
code
Maintenance description
1 Burner maintenance (burner operating hours)
2 Burner maintenance (burner starts)
3 Burner maintenance (General time interval: Months of service)
5 Lower pressure limit