Specifications

2-14
ELMo 120 Multiplexer installation and testin
g
Revision 2.01 ELMo 120 Multiplexer Installation and Maintenance Guide 08-01023-01
Task:
Installing ELMo 120 Multiplexer connections for
data-only service
Use this procedure to connect the ELMo 120 Multiplexer to the EtherLoop
cross-connect in applications where no voice service is required.
Requirements
This procedure requires the following tools and materials:
5-ELMo 120 Multiplexer cable harnesses
5-intermediate cables
cross-connect block(s) of the same type used in the existing main
distribution frame (MDF)
cross-connect punch-down tool
Appendix B contains the specifications for the cables and wiring required in
this procedure.
Action
Step Action
1
Place and secure the dedicated EtherLoop cross-connect blocks on the
facility main distribution frame.
2
Connect one Amp-Champ connector of an intermediate cable to the matchin
g
connector on the dedicated EtherLoop cross-connect block, and route the
other connector to the equipment bay containin
g
the ELMo 120 Multiplexer.
—continued—