4.9 Configure Local Alarms
To allow for local alarms using the ELAN local alarm interface you need to do the following.
Exit SENTINEL.
Find a free printer port on your computer
Add a 'generic printer' using the standard windows printer configuration and the free printer port.
Call the printer "Sentinel alarm'. Note: It must be called this exactly or SENTINEL will not work.
To use the local alarm, enable 'Local Alarms' on the 'configure alarms' window.
For each RCU that you require local alarms, configure the 'local alarm' bits required on the individual RCU
config window ( under the 'paging' tab ). When any alarm is received with local alarms enabled the selected
bits are bitwise OR'd together and output to the local alarm port.
Pressing the 'local alarm ack' button will clear all local alarms.
ELAN can provide a suitable relay box. This unit is called the SAR-01.
The connections for the parallel port must be as follows, or you will get printer errors from Windows.
Loop pins 1 to 10.
Loop pins 18, 11 and 12.
Grounds are pins 18 to 25.
Outputs are pins 2 to 9, alarm1 to alarm 8 respectively. TTL outputs active high.