Drawing : - TPC311 Issue :-6 Date : - 24/11/16 WM80 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 INTRODUCTION Designed for a wide range of applications, the WM80 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 SPECIFICATIONS MODEL: 10284GL-GB HEIGHT: 495mm WIDTH: 560mm DEPTH: 290mm WEIGHT: 37 kg AIRFLOW: 260 M3/Hr POWER SUPPLY: 230V - 50Hz - 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 3°C – 35°C REFRIGERANT: R407c (350g) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 OPERATION The following procedures should be followed to test the WM80 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 13 Amp electrical socket. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain. CAUTION: DO NOT REMOVE COVERS WHEN UNIT IS IN OPERATION 2.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 INSTALLATION The WM80 Dehumidifier can be left free standing unit, alternatively can be wall mounted for instructions on mounting the unit please read the following: A full installation kit is included in the package to allow a problem free install.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a Refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 TROUBLESHOOTING SYMPTOM Unit inoperative Little or no airflow Little or no water extraction Little or no defrost when required Unit vibrates excessively Water flooding inside the machine CAUSE REMEDY 1. Check the power from 1. No power to unit power supply panel 1. Tighten fan 1. Loose fan on shaft 2. Replace the fan motor 2. Fan motor burnt out 3. See Routine Maintenance 3. Dirty refrigeration coils / Section filter 4. Check the wiring diagram to 4.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 WM80 SPARE PARTS LIST DESCRIPTION NUMBER PART NUMBER QUANTITY 1 Filter 2028420 1 2 Timer 1601900 1 3 Evaporator Coil 2026074 1 4 Condenser Coil 2026014 1 5 Drain Tray 2131107 1 6 Capillary Tube 3014251 48” 7 Solenoid Valve 3020814 1 8 Filter Dryer 3020901 1 9 Compressor 3944918 1 10 Solenoid Coil 3030422 1 11 Capacitor 3037513 1 13 Fan Motor 3040198 1 16 Black Rubber Foot 3101436 4 17 Pump 3160146 1
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 300mm 300mm 300mm Page 10 of 12 300mm
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC311 Issue :-6 Date : - 24/11/16 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.