Drawing : - TPC543 Issue :-1 Date : - 28/04/21 EBAC MODEL WM80 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 WM80 PACKAGE CONTENTS Item Description Quantity 11284GL-US Dehumidifier 1 3082214 Brass wood screws 4 3088525 Rawl plug 4 3086144 Quick release hose coupling 1 3944110 PVC tube – 3/8” I/D 7.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 INTRODUCTION Designed for a wide range of applications, the WM80 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 SPECIFICATIONS MODEL: 11284GL-US HEIGHT: 19.4” (495mm) WIDTH: 22” (560mm) DEPTH: 11.4” (290mm) WEIGHT: 81.5 lbs (37Kg) AIRFLOW: 360 CFM (600M3/hr) POWER SUPPLY: 110V - 60Hz - 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 33°F – 105°F REFRIGERANT: R-407c (13 oz) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 OPERATION Once the appliance is installed turn the power supply on, then turn the on / off switch to the ‘I’ position, note the display will flash for approximately 1 second then show the humidity set point for approximately 12 seconds. Also all the indicator lights will illuminate for the same duration. After this brief period the display will show the room humidity and all the lights will go off.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 INSTALLATION The WM80 Dehumidifier can be left free standing unit, alternatively can be wall mounted for instructions on mounting the unit please read the following: A full installation kit is included in the package to allow a problem free install.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a Refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit Little or no airflow 1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils / filter 4. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 SPARE PARTS LIST Description Product Part Number PCB Timer Controls Display PCB Humidity Sensor PCB PCB Connecting Cable Condenser Coil Evaporator Coil Filter Mains Cable Keypad Label Drain Tray Insulation Tube 10mm ID Silicone Drain Tray Tube By-Pass Valve Filter Dryer Solenoid Coil 20mm Open Grommet 3/8” Open Grommet M16 Gland Nut Humidity Sensor Housing M16 Gland On / Off Switch Fan Motor Spire Clip No.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 300mm 300mm 300mm Page 11 of 16 300mm
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 LIMITED WARRANTY Our products carry a one-year unconditional warranty against any defects in workmanship or material. This warranty will cover all parts and labor required to repair your Ebac product. This warranty is invalid if the unit has been abused, damaged, whether intentional or accidental, or if any modifications have been made to the unit.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 Page 14 of 16
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 Page 15 of 16
Drawing : - TPC543 Issue :-1 Date : - 28/04/21 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.