Drawing : - TPC314 Issue :-5 Date : - 24/11/16 WM150 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact, slim design to provide easy efficient drying.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 SPECIFICATIONS MODEL: 10285GL-GB HEIGHT: 680mm WIDTH: 810mm DEPTH: 305mm WEIGHT: 75kg AIRFLOW: 580m3/hr POWER SUPPLY: 230V - 50Hz - 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 3°C – 35°C REFRIGERANT: R407c (540g) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 OPERATION The following procedures should be followed to test the WM150 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 13 Amp electrical socket. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain. CAUTION: DO NOT REMOVE COVERS WHEN UNIT IS IN OPERATION 2.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 INSTALLATION The WM150 Dehumidifier can be left free standing unit, alternatively can be wall mounted for instructions on mounting the unit please read the following: A full installation kit is included in the package to allow a problem free install.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a Refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 TROUBLESHOOTING SYMPTOM Unit inoperative Little or no airflow Little or no water extraction Little or no defrost when required Unit vibrates excessively Water flooding inside the machine CAUSE REMEDY 1. Check the power from 1. No power to unit power supply panel 1. Tighten fan 1. Loose fan on shaft 2. Replace the fan motor 2. Fan motor burnt out 3. See Routine Maintenance 3. Dirty refrigeration coils / Section filter 4. Check the wiring diagram to 4.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 WM150 SPARE PARTS LIST DESCRIPTION NUMBER PART NUMBER QUANTITY 1 Filter 2028517 1 2 Timer 1601200 1 3 Evaporator Coil 2028401 1 4 Condenser Coil 2028400 1 5 Humidistat 3035145 1 6 Capillary Tube 3014251 2 X 48” 7 Reversing Valve 3020810 1 8 Filter Dryer 3020904 1 9 Compressor 3944914 1 10 Solenoid Coil 3030419 1 Run Capacitor 11 (Compressor) 3037505 1 13 Fan Motor 3040242 1 16 Black Rubber Foot 3101436 4
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 300mm 300mm 300mm 300mm Recommended Minimum Distances Page 10 of 12
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC314 Issue :-5 Date : - 24/11/16 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.