Drawing : - TPC468 Issue :-2 Date : - 10/04/19 RM40 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 INTRODUCTION Designed for a wide range of applications, the RM40 is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying. The fan draws the moist air through the cold evaporator coil, which cools the air below its dew point. Moisture forms on the evaporator coil and is collected in the condensate tray, which is equipped with a permanent drain.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 SPECIFICATIONS MODEL: 10187MG-GB HEIGHT: 615 mm WIDTH: 382 mm DEPTH: 365 mm WEIGHT: 26 kg AIRFLOW: 185 M3/Hr POWER SUPPLY: 230V/ 50Hz/ 1 ph FINISH: Rotational Moulded polyethylene OPERATING RANGE: 3°C – 35°C REFRIGERANT: R410a (140g) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 OPERATION After unpacking, examine all external features to confirm damage-free shipment. Report all defects and damage at once. Before connecting it to the mains you should ensure that the humidistat is turned fully anti-clockwise. Connect to a grounded 13A electrical outlet then the humidistat control should be turned clockwise until you hear the unit operate.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 USE OF PERMANENT DRAINAGE When in use tubing should be run to a suitable drainage point, ensuring that the tube doesn’t rise above the drain tray, otherwise flooding may occur. CHECK DEHUMIDIFICATION PROCESS AS FOLLOWS: CAUTION: DO NOT REMOVE COVERS WHEN UNIT IS IN OPERATION 1. 2. 3. 4. 5. Place unit on a level surface. Start up unit by switching to “I” and humidistat fully clockwise Check that the compressor is running.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, service procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit 2. Mains cable damaged. Little or no airflow 1. Fan motor burnt out 2. Dirty refrigeration coils 3. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 RM40 SPARE PARTS LIST NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 DESCRIPTION Timer Refrigerant coil set Drain tray Filter Capillary Solenoid valve Filter dryer Solenoid coil On/Off switch Fan Motor Fan Blade Castor Compressor Water Container Assy Bucket Micro Switch Humidistat Knob Bucket Full Lens Bucket Full Light Humidistat Mains Cable Front Grille Page 9 of 12 PART NUMBER 1619506 2018743 2018705 1019712 3014251 3020836 3020937 3030452
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 Page 11 of 12
Drawing : - TPC468 Issue :-2 Date : - 10/04/19 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.