Drawing : - TPC321 Issue :-5 Date : - 24/11/16 DUAL VOLTAGE KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 INTRODUCTION Designed for a wide range of applications, the Kompact is a rugged, industrial unit, which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 SPECIFICATIONS MODEL: 10240KD-GB HEIGHT: 615mm WIDTH: 508mm DEPTH: 488mm WEIGHT: 40 kg AIRFLOW: 152 M3/Hr POWER SUPPLY: 230V/115V / 50Hz/ 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 3ºC – 35ºC REFRIGERANT: R407c (300g) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 OPERATION The following procedures should be followed to test the Kompact for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the unit to a suitable power supply and ensure the correct voltage has been selected. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain. 2.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit 2. Mains cable damaged. Little or no airflow 1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils 4. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 KOMPACT SPARE PARTS LIST DESCRIPTION NUMBER PART NUMBER QUANTITY 1 Filter 1019712 1 2 Timer 1600550 1 3 Evaporator Coil 2026074 1 4 Condenser Coil 2026014 1 5 Drain Tray 2131107 1 6 Capillary Tube 3014249 48” 7 Solenoid Valve 3020814 1 8 Filter Dryer 3020901 1 9 Compressor 3944921 1 10 Solenoid Coil 3030422 1 11 Capacitor 3030375 1 12 Terminal Block 3031460 1 13 Transformer 3031061 1 14 Fan Motor 30357
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 Page 10 of 12
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 Page 11 of 12
Drawing : - TPC321 Issue :-5 Date : - 24/11/16 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.