Drawing : - TPC374 Issue :-6 Date : - 24/11/16 ECO85 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 INTRODUCTION Designed for a wide range of applications, the ECO85 dehumidifier is a rugged, industrial unit which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 SPECIFICATIONS MODEL: ECO85 HEIGHT: 700mm WIDTH: 480mm DEPTH: 390mm WEIGHT: 40 kg 3 AIRFLOW: 650 M /Hr EXTRACTION: 30L / Day POWER SUPPLY: 230V/ 50Hz/ 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 3°C – 35°C REFRIGERANT: R-407c ( g) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 OPERATION The following procedures should be followed to test the CD85 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded electrical outlet. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain. 2.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit Little or no airflow 1. Fan motor burnt out 2. Dirty refrigeration coils 3. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2. Damaged fan Water flooding inside the machine 1.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 ECO85 SPARE PARTS LIST DESCRIPTION NUMBER PART NUMBER QUANTITY 1 Defrost Timer 1619508 1 2 Terminal Block 3031460 1 3 Capillary Tube 3014254 2 x 24” 4 Solenoid Valve 3020837 1 5 Filter Dryer 3020909 1 6 Compressor 3944918 1 7 Solenoid Coil 3030452 1 8 Capacitor 3037513 1 9 Filter 2029826 1 10 Mains Lead 2029217 1 11 3040253 1 12 Fan Motor Fan Motor Inlet Ring 3040254 1 13 Fan Motor Capacitor 3030841 1 14
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 Page 10 of 12
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 Page 11 of 12
Drawing : - TPC374 Issue :-6 Date : - 24/11/16 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.