FAN PERFORMANCE CURVES
For example:
If the total system resistance is 600pa then the process fan selector would
have to be set to No 10 to achieve the required airflow of 1200m³/h
For example:
If the total system resistance is 400pa then the regen fan selector would have
to be set to No 8 to achieve the required airflow of 330m³/h