Control Settings
Once the unit is positioned correctly, required duct work attached and the
power supply connected, the fan speeds and temperature control need to be
set correctly.
The fan speed controls are located behind a removable cover, to the right of
the main controls. The controls are numbered 1 to 10, with 10 being the
maximum speed.
The temperature control regulates the temperature of the reactivation airflow
onto the desiccant wheel. The control can be set up to a maximum of 145°C
To adjust the temperature control simply press the ‘SET’ button and then
select the required setting by using the
▲ or ▼ buttons. To confirm press the
button and the value is stored. The display will revert back to the current
temperature.
For normal (efficient) operation the process airflow should be set to 1200m³/h,
and the regeneration airflow set to 330m³/h. Measurements should be taken
at the duct outlets using a suitable instrument.
The temperature setting should be set to 90°C above the ambient
temperature of the area being dehumidified
If high moisture extraction is required it will be necessary to increase both the
process and regeneration airflows. The temperature control setting should
also be increased.
If very low humidity levels are required then the process airflow should be
reduced.
The following table should be used as a guide:
PROCESS AIR
FLOW
(M³/H)
REGEN AIR
FLOW
(M³/H)
TEMPERATURE
RISE
(K)
STANDARD
(EFFICIENT)
1200 330 90
HIGH
EXTRACTION
1400 400 110
DEEP DRYING
(LOW RH)
1000 400 110