IF ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC
INDUSTRIAL PRODUCTS LTD SERVICE CENTER PRIOR TO CONTINUED
OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE
.
TROUBLESHOOTING
SYMPTOM
CAUSE
REMEDY
Little or no
dehumidification
capacity
Filter clogged
Clean or replace filters
No regeneration heat Check Heaters / OHP
Reduced airflow Check fans / duct
No rotation of Rotor Check belt tension / drive motor
Air leakage Check sealing
Dehumidifier does
not start
No power Check fuse
Correct switch setting Check Auto / Manual switch
Loose electrical wiring
Check wiring diagram - fault
find & repair
Rotor does not
rotate
Drive belt slipping Check belt tension
Drive belt broken Replace drive belt
Rotor jammed Check centre shaft, rim of rotor
Drive motor faulty Check supply /Replace motor
No Dry or Wet Air
Airflow
Filter clogged Clean or replace filters
Fan faulty Check supply / fan
Ducts blocked Check duct for obstruction
Noisy
Fan loose Check fans secured firmly
Loose fastenings Tighten all fastenings