Drawing : - TPC302 Issue :-7 Date : - 10/12/13 CS60 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 CS60 PACKAGE CONTENTS Item Description Quantity 10264CS-US Dehumidifier 1 3014338 PVC tube – 12mm I/D 3M 3086101 Jubilee clip 1 TPC302 Manual 1 Page 2 of 12
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 INTRODUCTION Designed for a wide range of applications, the CS60 dehumidifier is a rugged, industrial unit which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 SPECIFICATIONS MODEL: CS60 HEIGHT: 14” (355mm) WIDTH: 14” (355mm) DEPTH: 20” (508mm) WEIGHT: 63lbs (28.5 kg) AIRFLOW: 360 CFM (608M3/hr) EXTRACTION: 56 Pints Per Day POWER SUPPLY: 110V/ 60Hz/ 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 33°F – 95°F REFRIGERANT: R-407c (13 oz) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 OPERATION The following procedures should be followed to test the CS60 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 15 Amp electrical outlet. 2. Check dehumidification process as follows: TO ENSURE CONTINUED FULL EFFICIENCY OF THE DEHUMIDIFEIR, MAINTENANCE PROCEDURES SHOULD BE PERFORMED AS FOLLOWS: A.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 ROUTINE MAINTENANCE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTNENANCE To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil to avoid damaging the fins.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit Little or no airflow 1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils 4. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 CS 60 SPARE PARTS LIST NUMBER DESCRIPTION PART NUMBER QUANTITY 1 Defrost Timer 1600550 1 2 Control Knob 2019708 1 3 Capillary Tube 3014251 48” 4 Solenoid Valve 3020814 1 5 Filter Dryer 3020901 1 6 Compressor 3022169 1 7 Solenoid Coil 3030421 1 8 Capacitor 3030908 1 9 Humidistat 3035145 1 10 Mains Lead 3035148 1 3035753 1 12 Fan Motor & Blade Assembly Relay 3036157 1 13 Rubber Foot 3101436 1 14 Drain Tubin
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 LIMITED WARRANTY Our products carry a one-year unconditional warranty against any defects in workmanship or material. This warranty will cover all parts and labor required to repair your Ebac product. This warranty is invalid if the unit has been abused, damaged, whether intentional or accidental, or if any modifications have been made to the unit.
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 Page 11 of 12
Drawing : - TPC302 Issue :-7 Date : - 10/12/13 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.