Drawing : - TPC361 Issue :-7 Date : - 09/03/15 CD85 INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 CD85 PACKAGE CONTENTS Item Description Quantity 10293GR-US Dehumidifier 1 3014338 PVC Tube – 12mm I/D 3M 3086101 Jubilee clip 1 3090150 Handle 2 TPC361 Manual 1 Page 2 of 16
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 INTRODUCTION Designed for a wide range of applications, the CD85 dehumidifier is a rugged, industrial unit which utilizes an energy-efficient compressor and a compact portable design to provide easy efficient drying.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 COVERS The CD85 covers can be swapped to allow the airflow direction to be changed to better suit the application the unit is to be used for. To change the covers, first remove the 4 off retaining screws and washers from each cover, swap cover positions and replace 4 off retaining screws and washers. If changing the evaporator covers then the filter retaining mesh should always be placed behind the Evaporator Grille Cover.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 Evaporator Blank Cover (Blocks Airflow) Condenser Grille Cover (Air out of machine) Condenser Blank Cover (Blocks airflow) Evaporator Grille Cover (Air into Machine) Evaporator Blank Cover (Blocks Airflow) Condenser Blank Cover (Blocks airflow) Evaporator Grille Cover (Air into Machine) Condenser Grille Cover (Air out of Machine) HANDLE The CD85 can be fitted with handles if required. Handles are found separate in the packaging.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 SPECIFICATIONS MODEL: CD85 HEIGHT: 15.75” WIDTH: 23.6” DEPTH: 13.5” WEIGHT: 75 lbs AIRFLOW: 360 CFM EXTRACTION: 56 Pints Per Day POWER SUPPLY: 110V/ 60Hz/ 1 ph FINISH: Powder-coated Epoxy OPERATING RANGE: 33°F – 95°F REFRIGERANT: R-407c (17.64 oz) "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 OPERATION The following procedures should be followed to test the CD85 for correct operation: 1. After unpacking, examine all external features to confirm damagefree shipment. Report all defects and damage at once. Connect the power cable to a grounded 15 Amp electrical outlet. 2. Check dehumidification process as follows: TO ENSURE CONTINUED FULL EFFICIENCY OF THE DEHUMIDIFEIR, MAINTENANCE PROCEDURES SHOULD BE PERFORMED AS FOLLOWS: A.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 ROUTINE MAINTENANCE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE MAINTNENANCE To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil to avoid damaging the fins.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 TROUBLESHOOTING SYMPTOM CAUSE Unit inoperative 1. No power to unit Little or no airflow 1. Fan motor burnt out 2. Dirty refrigeration coils 3. Loose electrical wiring Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Little or no defrost when required 1. Faulty timer 2. Faulty by-pass valve Unit vibrates excessively 1. Loose compressor 2. Damaged fan Water flooding inside the machine 1.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 CD85 SPARE PARTS LIST DESCRIPTION NUMBER PART NUMBER QUANTITY 1 Defrost Timer 1619508 1 2 Thermistor assembly 3035142 1 2 Control Knob 2018644 1 3 Capillary Tube 3014254 2 x 24” 4 Solenoid Valve 3020814 1 5 Filter Dryer 3020909 1 6 Compressor 3022198 1 7 Solenoid Coil 3030421 1 8 Capacitor 3030908 1 9 Humidistat 3035147 1 10 Mains Lead 3035148 1 11 3040262 1 12 Fan Motor Fan Motor Inlet Ring 3040254 1 13
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 LIMITED WARRANTY Our products carry a one-year unconditional warranty against any defects in workmanship or material. This warranty will cover all parts and labor required to repair your Ebac product. This warranty is invalid if the unit has been abused, damaged, whether intentional or accidental, or if any modifications have been made to the unit.
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 Page 13 of 16
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 Page 14 of 16
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 Page 15 of 16
Drawing : - TPC361 Issue :-7 Date : - 09/03/15 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.