Manual
Page 4 of 16
Drawing : - TPC127A
Issue : - 5
Date : - 23/11/16
INSTALLATION
POSITIONING:
The CD425 is designed for indoor use only.
Position the dehumidifier unit in the centre of the room to be conditioned if at
all possible. Using a spirit level ensure the unit is level in both directions.
Failure to do so may result in the drain tray overflowing and flooding of the
chamber.
NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have
clear space around them and not be obstructed in anyway.
Minimum installation requirements.
A gap of at least 1000mm is required above the dehumidifier.
AIR IN
AIR IN
AIR OUT
1000mm
1000mm
250mm
25
0mm