Drawing : - TPC500 Issue :-1 Date : - 29/01/20 CD30SE INDUSTRIAL DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 CD30SE PACKAGE CONTENTS Item Description Quantity 1142050 Dehumidifier 1 1139504 Wall mount bracket 1 3082214 Brass wood screw 3 3088525 Rawl plug 3 3014338 PVC tube – 12mm I/D 3M 3086101 Jubilee clip 1 TPC500 Manual 1 Page 2 of 12
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 UNPACKING Carefully remove the CD30SE dehumidifier unit from its transit box and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing; it will be useful when transporting the dehumidifier unit in the future. INTRODUCTION The Ebac CD30SE industrial dehumidifier removes moisture from the air through the refrigeration process.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 SPECIFICATIONS MODEL: CD30SE HEIGHT: 12” WIDTH: 12” DEPTH: 22” WEIGHT: 55 lbs AIRFLOW: 170 CFM MAX OPERATING TEMP: 95ºF POWER SUPPLY: 110V, 60Hz CURRENT: 3 A REFRIGERANT TYPE: R134a "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 OPERATION The operation of the dehumidifier is to remove moisture from the air by having it condense on the cold tubes of the evaporator coil. The air then passes over the hot condenser coil and returns to the conditioned space slightly warmer and dryer than when it entered the dehumidifier unit. TEST FOR CORRECT OPERATION The following procedures should be followed to test the CD30SE for correct operation. 1.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 SPECIAL FEATURES Control Humidistat This humidistat operates in the same way as the normal humidistat to control the on/off function of the dehumidifier units, but is factory pre-set at 55% RH to maintain the relative humidity air at the set point. Alarm Humidistat This humidistat, which has been factory pre-set at 70% RH, allows for connection to an external warning system.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1. Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 TROUBLESHOOTING SYMPTOM CAUSE REMEDY 1. Check the power from the power supply panel. 1. Tighten fan 2. Replace the fan motor 3. See Routine Maintenance Section 4. Check the wiring diagram to find fault and repair 1. Check all of the above 2. Contact the Factory Service Center 3. Contact the Factory Service Center 4. Contact the Factory Service Center 1. Contact the Factory Service Center 2. Contact the Factory Service Center Unit inoperative 1.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 CD30SE SPARE PARTS LIST DESCRIPTION QTY PART NUMBER Compressor 1 3944958 Refrigeration Coil Set 1 3020740 Evaporator Coil 1 2139528 Fan Motor 1 3035773 Fan Blade 1 3040129 Timer Board 1 1619519 Humidistat 1 3035145 Humidistat Knob 1 3030421 Solenoid Coil 1 3020421 Defrost By-Pass Valve 1 3020811 Filter Dryer 1 3020937 Cover Assembly 1 1013703 Page 10 of 12
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC500 Issue :-1 Date : - 29/01/20 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.