Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 UNPACKING Carefully remove the CD200 dehumidifier unit from its transit packaging and visually check for signs of transit damage. If there is evidence of damage DO NOT attempt to operate the unit, call your supplier for advice. Do not discard the packing, it will be useful when transporting the dehumidifier unit in the future. INTRODUCTION The Ebac CD200 industrial dehumidifier removes moisture from the air through the refrigeration process.
Drawing No.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 INSTALLATION POSITIONING: Position the dehumidifier unit in the centre of the room to be conditioned if at all possible. However if a damp patch is particularly apparent the outlet grille should be pointed towards it if possible. NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have clear space around them and not be obstructed in anyway. This unit should be connected to a single outlet circuit fused spur with a 20A rating.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 OPERATION The following procedures should be followed to test the CD200 for correct operation: 1) After unpacking, examine all external features to confirm damage-free shipment. Report all defects and damage at once. Connect the power cable to a grounded power source. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 External Humidistat Option The CD200 has the option of using an external humidistat remotely mounted within a room, where available. In the control box there is a connector that can be wired to, which will enable the use of an external humidistat. The following steps should be carried out to enable correct operation of the external humidistat.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: 1.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 TROUBLESHOOTING REMEDY SYMPTOM CAUSE Unit inoperative 1. no power to unit Little or no airflow 1. 2. 3. 4. Little or no water extraction 1. Insufficient air flow 2. Compressor fault 3. Loss of refrigerant gas Unit vibrates excessively 1. Loose compressor mounts 2. Damaged fan Water flooding inside the machine 1. Drain pipe blocked/frozen 2.
Drawing No.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing No.
Drawing No.
A B C D 6 6 157 192.3 112.5 5 445 220 5 50 AIR OUT 4 4 AIR IN 305 417.1 800 50 107.5 3 DO NOT SCALE IF IN DOUBT ASK 3RD ANGLE PROJECTION 19 9 7 3 06/07/11 09/09/11 1 2 2 2 MATERIAL DIMENSIONS IN m.m. TOLERANCES UNLESS OTHERWISE STATED 0. 1 FINISH 0.25 0.0 0.05 0.00 ANGULAR 0.5 DEGREE TITLE 1 N/A N/A 1 1/5 SHEET 1 OF 1 W DAGLISH 1018211 DRG.NO. CAD SCALE : DRAWN : CD200 DUCT FLANGE LOCATIONS AIR DIRECTION ADDED - WDA ORIGINAL COMMENTS BISHOP AUCKLAND Co.
A B C D 6 6 CONDENSATE OUTLET DUCT FLANGE 530mm WIDE X 305mm HIGH X 50mm DEEP 5 5 4 TOP VIEW OF CD200 AIRFLOW 4 POWER CORD FILTER INSERTED THIS SIDE AS REQUIRED INLET DUCT 3 21/12/10 1 AIRFLOW DATE ISS. 2 OUTLET DUCT ORIGINAL COMMENTS DO NOT SCALE IF IN DOUBT ASK TITLE 2 MATERIAL DIMENSIONS IN m.m. TOLERANCES UNLESS OTHERWISE STATED 0. 1 FINISH 0.25 0.0 0.05 0.00 ANGULAR 0.5 DEGREE BISHOP AUCKLAND Co.
Drawing No. :- TPC365 Issue :- 7 Date :- 24/11/16 UK Head Office American Sales Office German Sales Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD Ebac Industrial Products Inc 700 Thimble Shoals Blvd. Suite 109, Newport News Virginia, 23606-2575 USA Ebac Industrial Products Ltd. Gartenfelder Str.