Drawing : - TPC385 Issue :-4 Date : - 24/11/16 CD100 DEHUMIDIFIER OWNER’S MANUAL www.eipl.co.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 INTRODUCTION Dehumidifiers remove moisture from the air that is circulating through the unit. The resulting reduction of relative humidity helps prevent rust, rot, mould, mildew and condensation within the room, or other enclosed spaces where the dehumidifier is used.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 SPECIFICATIONS MODEL: CD100 HEIGHT: 400mm WIDTH: 1130mm DEPTH: 500mm WEIGHT: 75 Kg AIRFLOW: 510 M3/hr POWER SUPPLY: UK-220V/240V, 1 ph, 50Hz/60Hz POWER 1500 W (max) FINISH: Vinyl coated steel REFRIGERANT TYPE/QTY: R407c (540g) MOBILITY: Choice of aids – wheels or skid handles "This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 INSTALATION POSITIONING: Position the dehumidifier unit in the center of the room to be conditioned if at all possible. However if a damp patch is particularly apparent the outlet grille should be pointed towards it. NOTE: Both inlet grille and outlet grille of the dehumidifier unit must have clear space around them and not be obstructed in anyway. For correct installation and operation the unit inlet and outlet must have a clearance of 0.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 OPERATION The operation of the dehumidifier is to remove moisture from the air by having it condense on the cold tubes of the evaporator coil. The air then passes over the hot condenser coil and returns to the conditioned space slightly warmer and dryer than when it entered the dehumidifier unit. To concentrate drying all doors and windows should be kept closed.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 approximately 50% for factories and warehouses and for basements or deflooding then the humidistat should be set to approximately 100%. Optional Discharge Pump This is an optional extra as requested at purchase. The pump works automatically and periodically pumps away collected moisture to a drain or container. The pump is capable of discharging water to a vertical height of 30ft.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 ROUTINE SERVICE WARNING: ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON. To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows: Removal of the cover is achieved by means of four screws at the sides of the unit at base level.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 REPAIRS 1. Should an electrical component fail, consult the Factory Service Center to obtain the correct replacement part. 2. If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action. Any competent refrigeration technician will be able to service the equipment. The following procedure must be used: a.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 TROUBLESHOOTING SYMPTOM CAUSE REMEDY 1. Tighten fan 2. Replace the fan motor 3. See Routine Maintenance Section 4. Check the wiring diagram to find fault and repair 1. Check all of the above 2. Contact the Factory Service Center 3. Contact the Factory Service Center 1. Contact the Factory Service Center 2. Contact the Factory Service Center Little or no airflow 1. Loose fan on shaft 2. Fan motor burnt out 3. Dirty refrigeration coils 4.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 WARNINGS This appliance can be used by children from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the application in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 Page 11 of 12
Drawing : - TPC385 Issue :-4 Date : - 24/11/16 UK Head Office Ebac Industrial Products Ltd St Helens Trading Estate Bishop Auckland County Durham DL14 9AD American Sales Office German Sales Office Ebac Industrial Products Inc Ebac Industrial Products Ltd. 700 Thimble Shoals Blvd. Gartenfelder Str.