Drawing : - TPC449
Issue : - 2
Date : - 02/11/16
ROUTINE SERVICE
To ensure continued full efficiency of the dehumidifier, maintenance
procedures should be performed as follows:
1. Clean the surface of the evaporator and condenser coils by blowing
the dirt out from behind the fins with compressed air. Hold the nozzle
of the air hose away from the coil to avoid damaging the fins.
Alternatively, vacuum clean the coils.
2. Check that the fan is firmly secured to the motor shaft and that the
fan rotates freely. The fan motor is sealed for life and therefore
does not need oiling.
3. To check the refrigerant charge, run the unit for 15 minutes. The
evaporator coil should be evenly frost coated across its surface. At
temperatures above 25°C, the coil may be covered with droplets of
water rather than frost. Partial frosting accompanied by frosting of
the thin capillary tubes, indicates loss of refrigerant gas or low
charge.
4. Check all wiring connections.
5. To check the operation of the defrost system, switch the machine on
and leave it running for approximately 42 minutes. The machine will
then enter Reverse Cycle defrost mode for approximately 4 minutes
before returning to normal operation. If the unit will not defrost, the
printed circuit timer board may be defective or the by-pass valve may
be inoperable.
I
F ANY OF THE PRECEDING PROBLEMS OCCUR
,
CONTACT THE
E
BAC
S
ERVICE
C
ENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO
PREVENT PERMANENT DAMAGE
.
WARNING:
ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN
DISCONNECTED BEFORE CARRYING OUT ROUTINE SERVICE.
THE SERVICING AND REPAIR OF THIS UNIT SHOULD ONLY BE
CARRIED OUT BY A SUITABLY QUALIFIED PERSON.
WARNING:
DO NOT STEAM CLEAN REFRIGERATION COILS