Servo control
3.7 Current setpoint filter
Drive Functions
78 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Current controller adaptation
p0391[0...n] Current controller adaptation lower starting point
p0392[0...n] Current controller adaptation upper starting point
p0393[0...n] Current controller adaptation upper P gain
p1590[0...n] Flux controller P gain
p1592[0...n] Flux controller integral time
3.7 Current setpoint filter
Description
The four current setpoint filters connected in series can be parameterized as follows:
Low-pass 2nd order (PT2: -40 dB/decade) (type 1)
General filter 2nd order (type 2)
Bandstop and lowpass with reduction are converted to the parameters of the general filter
2nd order via STARTER.
Bandstop
Low-pass with reduction by a constant value
The phase frequency curve is shown alongside the amplitude log frequency curve. A phase
shift results in a control system delay and should be kept to a minimum.