- Siemens Cordless Telephone User Manual

Basic information about the drive system
12.7 Examples of replacing components
Drive Functions
500 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Action Reaction Comments
Load the project from the
Control Unit to the
STARTER (PG)
Configure the replacement
drive and select the current
component
Load the project to the
Control Unit (target system)
Alarm disappears
The new order number is stored
in the RAM of the Control Unit
and has to be copied to the non-
volatile memory with p0971 or
p0977.
The component has been successfully replaced
Example: (p9909 = 1) Replacing a defective component with an identical order number
Precondition:
The replaced component has an identical order number
The serial number of the new replacement component must not be contained in the
stored target topology of the Control Unit.
Topology comparison component replacement active p9909 = 1.
Sequence:
During startup of the Control Unit, the serial number of the new component is automatically
transferred to the target topology and saved.
Example: (p9909 = 0) Replacing a defective component with an identical order number
Precondition:
The replaced component has an identical order number
Topology comparison component replacement inactive p9909 = 0.
Table 12-12 Example: Replacing a Motor Module
Action Reaction Comments
Switch off the power supply
Replace the defective
component and connect the
new one
Switch on the power supply
Alarm A01425