r0896.0 BO: Parking axis status word
p0151 DRIVE-CLiQ Hub component number
p0154 DRIVE-CLiQ Hub identification using LED
p0157 DRIVE-CLiQ Hub EPROM data version
r0158 DRIVE-CLiQ Hub firmware version
11.5 Control Units without infeed control
11.5.1 Description
Description
To ensure that the drive line-up functions satisfactorily, you must ensure – among other
things – that the drives only draw power from the DC link when the infeed is in operation. In a
DC link line-up that is controlled by just one Control Unit and in which a drive object has an
infeed, the BICO interconnection p0864 = p0863.0 is established automatically during
commissioning.
In the following cases, the BICO input p0864 must be supplied manually:
Smart Line Modules without DRIVE-CLiQ (5 kW and 10 kW)
DC link line-up with more than one Control Unit