Infeed
1.4 Line contactor control
Drive Functions
42 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Control and status messages
Table 1-7 Basic Infeed open-loop control
Signal name Internal control word Binector input Display of internal
control word
PROFIdrive telegram
370
ON/OFF1 STWAE.0 p0840 ON/OFF1 r0898.0 A_STW1.0
OFF2 STWAE.1 p0844 1 OFF2 and
p0845 2 OFF2
r0898.1 A_STW1.1
Acknowledge error STWAE.7 p2103 1 Acknowledge
or
p2104 2 Acknowledge
or
p2105 3 Acknowledge
r2138.7 A_STW1.7
Master ctrl by PLC STWAE.10 p0854 Master ctrl by
PLC
r0898.10 A_STW1.10
Table 1-8 Basic Infeed status message
Signal name Internal status word Parameter PROFIdrive telegram 370
Ready to power up ZSWAE.0 r0899.0 A_ZSW1.0
Ready to run ZSWAE.1 r0899.1 A_ZSW1.1
Operation enabled ZSWAE.2 r0899.2 A_ZSW1.2
No OFF2 active ZSWAE.4 r0899.4 A_ZSW1.4
Power-on disable ZSWAE.6 r0899.6 A_ZSW1.6
Master ctrl by PLC ZSWAE.9 r0899.9 A_ZSW1.9
Pre-charging completed ZSWAE.11 r0899.11 A_ZSW1.11
Line contactor energized
feedback
ZSWAE.12 r0899.12 A_ZSW1.12
1.4 Line contactor control
Description
This function can be used to control an external line contactor. Opening and closing the line
contactor can be monitored by evaluating the feedback contact in the line contactor. The line
contactor is used for the electrical isolation of the DC link for the energy supply network.
The line contactor can be controlled using the following drive objects:
Via bit r0863.1 of drive object INFEED
Via bit r0863.1 of drive object SERVO/VECTOR
Note
For more information on the line connection, see the Equipment Manuals.