Communication PROFIBUS DP/PROFINET IO
10.2 Communication via PROFIBUS DP
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
415
Field Value
No. of elements 1
Decimal places Any
Note
You can operate a SIMATIC HMI together with a drive unit independently of an existing
control.
A basic "point-to-point" connection can only be established between two nodes (devices).
The "variable" HMI functions can be used for drive units. Other functions cannot be used
(e.g. "messages" or "recipes").
Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot
be accessed.
10.2.2.5 Monitoring: telegram failure
Description
After a telegram failure and a monitoring time has elapsed (t_An), bit r2043.0 is set to "1"
and alarm A01920 is output. Binector output r2043.0 can be used for an emergency stop, for
example.
After a delay time has elapsed (p2044), fault F01910 is output. Fault F01910 triggers fault
response OFF2 (pulse inhibit) for the supply and fault response OFF3 (emergency stop) for
SERVO/VECTOR. If no OFF response is to be triggered, the fault response can be
reparameterized accordingly.
Fault F01910 can be acknowledged immediately. The drive can then be operated even
without PROFIBUS.