Communication PROFIBUS DP/PROFINET IO
10.2 Communication via PROFIBUS DP
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
411
References: /GH1/ SINAMICS S120 Equipment Manual for Control Units and Additional
System Components
PROFIBUS diagnostic LED
Note
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnosis purposes.
Setting the PROFIBUS address
Two methods are available for setting the PROFIBUS address:
1. Via the PROFIBUS address switches on the Control Unit
In this case, p0918 is read-only and simply displays the set address.
A change is not effective until POWER ON.
2. Via p0918
You can only use this method when all the PROFIBUS address switches from S1 to
S7 are set to ON or OFF.
Address changes made via parameters must be saved in a non-volatile memory using
the "Copy from RAM to ROM" function.
A change is not effective until POWER ON.
Example:
Setting the PROFIBUS address using the PROFIBUS address switches on the Control Unit.