Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
398 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Error
value
Meaning Comment Additional
info
0x78 Parameter %s [%s]: Write access
only in the commissioning state, drive
configuration (device: p0009 = 3).
– –
0x79 Parameter %s [%s]: Write access
only in the commissioning state,
define drive type (device: p0009 = 2).
– –
0x7A Parameter %s [%s]: Write access
only in the commissioning state, data
set basis configuration
(device: p0009 = 4).
– –
0x7B Parameter %s [%s]: Write access
only in the commissioning state,
device configuration
(device: p0009 = 1).
– –
0x7C Parameter %s [%s]: Write access
only in the commissioning state,
device download
(device: p0009 = 29).
– –
0x7D Parameter %s [%s]: Write access
only in the commissioning state,
device parameter reset
(device: p0009 = 30).
– –
0x7E Parameter %s [%s]: Write access
only in the commissioning state,
device ready (device: p0009 = 0).
– –
0x7F Parameter %s [%s]: Write access
only in the commissioning state,
device (device: p0009 not 0).
– –
0x81 Parameter %s [%s] may not be
written in download.
– –
0x82 Transfer of the control authority
(master) is inhibited by BI: p0806.
– –
0x83 Parameter %s [%s]: requested BICO
interconnection not possible
BICO output does not supply float values. The BICO input,
however, requires a float value.
–
0x84 Parameter %s [%s]: parameter
change inhibited
(refer to p0300, p0400, p0922)
– –
0x85 Parameter %s [%s]: access method
not defined.
– –
0xC8 Below the valid values. Modification request for a value that, although within
"absolute" limits, is below the currently valid lower limit.
–
0xC9 Above the valid values. Modification request for a value that, although within
"absolute" limits, is below the currently valid lower limit
(e.g. governed by the current converter rating).
–
0xCC Write access not permitted. Write access is not permitted because an access key is
not available.
–