Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
397
Error
value
Meaning Comment Additional
info
0x15 Response too long The length of the present response exceeds the maximum
transfer length.
–
0x16 Illegal parameter address Impermissible or unsupported value for attribute, number
of elements, parameter number, subindex or a
combination of these.
–
0x17 Illegal format Write request: illegal or unsupported parameter data
format
–
0x18 No. of values inconsistent Write request: a mismatch exists between the number of
values in the parameter data and the number of elements
in the parameter address.
–
0x19 Drive object does not exist You have attempted to access a drive object that does not
exist.
–
0x65 Presently deactivated. You have tried to access a parameter that, although
available, is currently inactive (e.g. n control set and
access to parameter from V/f control).
–
0x6B Parameter %s [%s]: no write access
for the enabled controller
– –
0x6C Parameter %s [%s]: unit unknown – –
0x6D Parameter %s [%s]: Write access
only in the commissioning state,
encoder (p0010 = 4).
– –
0x6E Parameter %s [%s]: Write access
only in the commissioning state,
motor (p0010 = 3).
– –
0x6F Parameter %s [%s]: Write access
only in the commissioning state,
power unit (p0010 = 2).
– –
0x70 Parameter %s [%s]: Write access
only in the quick commissioning
mode (p0010 = 1).
– –
0x71 Parameter %s [%s]: Write access
only in the ready mode (p0010 = 0).
– –
0x72 Parameter %s [%s]: Write access
only in the commissioning state,
parameter reset (p0010 = 30).
– –
0x73 Parameter %s [%s]: Write access
only in the commissioning state,
Safety (p0010 = 95).
– –
0x74 Parameter %s [%s]: Write access
only in the commissioning state, tech.
application/units (p0010 = 5).
– –
0x75 Parameter %s [%s]: Write access
only in the commissioning state
(p0010 not equal to 0).
– –
0x76 Parameter %s [%s]: Write access
only in the commissioning state,
download (p0010 = 29).
– –
0x77 Parameter %s [%s] may not be
written in download.
– –