Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
383
Error code in Gn_XIST2
Table 10-20 Error code in Gn_XIST2
n_XIST2 Meaning Possible causes / description
1 Encoder error One or more existing encoder faults.
Detailed information in accordance with drive messages.
2 Zero marker monitoring
3 Abort parking sensor
Parking drive object already selected.
4 Abort find reference
marker
A fault exists (Gn_ZSW.15 = 1)
Encoder has no zero marker (reference marker)
Reference marker 2, 3 or 4 is requested
Switchover to "Measurement on-the-fly" during search for reference marker
Command "Read value x" set during search for reference marker
Inconsistent position measured value with distance-coded reference markers.
5 Abort, retrieve reference
value
More than four values requested
No value requested
Requested value not available
6 Abort flying measurement
No probe configured p0488, p0489
Switch over to "reference mark search" during flying measurement
Command "Read value x" set during flying measurement
7 Abort get measured value
More than one value requested
No value requested.
Requested value not available
Parking encoder active
Parking drive object active
8 Abort absolute value
transmission on
Absolute encoder not available
Alarm bit absolute value protocol set
3841 Function not supported
Encoder 2 status word (G2_STW)
See G1_STW (table 4-20)
Encoder 2 actual position value 1 (G2_XACT1)
See G1_XIST1
Encoder 2 actual position value 2 (G2_XACT2)
See G1_XIST2
Encoder 3 status word (G3_STW)
See G1_STW (table 4-20)