10.1 Communications according to PROFIdrive
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
381
Bit Name Signal status, description
0 No active parking encoder
1 Error from encoder or actual-value sensing is active.
Note:
The error code is stored in Gn_XACT2.
15 Encoder error
0 No error is active.
Encoder 1 actual position value 1 (G1_XACT1)
Resolution: Encoder lines ∙ 2n
n: fine resolution, no. of bits for internal multiplication
The fine resolution is specified via p0418.
Used to transmit the cyclic actual position value to the controller.
The transmitted value is a relative, free-running actual value.
Any overflows must be evaluated by the master controller.
)LQHLQIRUPDWLRQ(QFRGHUOLQHV
,QWHUQDOPXOWLSOLFDWLRQ
)DFWRU\VHWWLQJ
SIRU*[B;,67HQFRGHUWR

%LWb
Figure 10-14 Subdivision and settings for Gx_XIST1
Encoder lines of incremental encoder
For encoders with sin/cos 1Vpp:
Encoder lines = no. of sinusoidal signal periods
After power-up: Gx_XIST1 = 0
An overflow in Gx_XIST1 must be viewed by the master controller.
There is no modulo interpretation of Gx_XIST1 in the drive.
Encoder 1 actual position value 2 (G1_XACT2)
Different values are entered in Gx_XACT2 depending on the function.
Priorities for Gx_XIST2
The following priorities should be considered for values in Gx_XIST2: