- Siemens Cordless Telephone User Manual

Infeed
1.3 Basic Infeed
Drive Functions
38 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Signal name Internal status
word
Parameter PROFIdrive telegram 370
Pre-charging completed ZSWAE.11 r0899.11 A_ZSW1.11
Line contactor energized feedback ZSWAE.12 r0899.12 A_ZSW1.12
1.3 Basic Infeed
1.3.1 Basic Infeed open-loop control
General
Note
Line Modules (Active Line Modules, Basic Line Modules, Smart Line Modules) of different
types must not be operated simultaneously on the same DC link.
Features
For Basic Line Modules Chassis and Booksize
Unregulated DC link voltage
Intregrated control of external braking resistors with 20 kW and 40 kW Basic Line
Modules (with temperature monitoring)
Description
Basic Infeed open-loop control can be used to switch on/off the Basic Line Module. The
Basic Line Module is an unregulated infeed unit without regenerative feedback capability.
The open-loop control firmware for the Basic Line Module runs on the Control Unit assigned
to it. The Basic Line Module and Control Unit communicate via DRIVE-CLiQ.