Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
353
Function diagrams (see SINAMICS S List Manual)
2410 PROFIBUS address, diagnostic
...
2483 Send telegram, free interconnection via BICO (p0922 = 999)
10.1.3.2 Monitoring: telegram failure
Description
After a telegram failure and a monitoring time has elapsed (p2047), bit r2043.0 is set to "1"
and alarm A01920 is output. Binector output r2043.0 can be used for an emergency stop, for
example.
After a delay time has elapsed (p2044), fault F01910 is output. Fault F01910 triggers fault
response OFF2 (pulse inhibit) for the supply and fault response OFF3 (emergency stop) for
SERVO/VECTOR. If no OFF response is to be triggered, the fault response can be
reparameterized accordingly.
Fault F01910 can be acknowledged immediately. The drive can then be operated even
without PROFIdrive.
&\FOLFWHOHJUDPV
IURPPDVWHU
)
W
64
54
$
U
S
7
S
7
Figure 10-8 Monitoring: telegram failure
Example: emergency stop with telegram failure
Assumption:
A drive unit with an Active Line Module and a Single Motor Module.
VECTOR mode is activated.
After the ramp-down time has elapsed (p1135), the drive is at a standstill.
Settings:
CU p2047 = 20 ms
A_INF p2044 = 2 ms
VECTOR p2044 = 0 ms
Sequence:
After a telegram failure and the monitoring time has elapsed (p2047), binector output r2043.0
of drive object CU switches to "1". At the same time, alarm A01920 is output for the A_INF