Safety Integrated basic functions
9.8 Acceptance test and certificate
Drive Functions
330 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
No. Description Status
The following is tested:
Correct DRIVE-CLiQ wiring between Control Unit and Motor Modules
Correct assignment of drive No. – Motor Module – motor
The hardware is functioning properly
The switch-off signal paths are wired correctly
Correct assignment of the terminals for STO on the Control Unit
Correct STO grouping (if available)
Correct parameterization of the STO function
Routine for forced dormant error detection of the switch-off signal paths
9.8.4 Acceptance test for Safe Stop 1, time controlled (SS1)
"Safe Stop 1" function (SS1, time-controlled)
This test comprises the following steps:
Table 9-11 "Safe Stop 1" function (SS1)
No. Description Status
Initial state
Drive in "Ready" status (p0010 = 0)
STO function enabled (p9601.0 = 1, p9801.0 = 1)
Enable SS1 function (p9652 > 0, p9852 > 0)
No safety faults and alarms (r0945, r2122, r2132)
r9772.0 = r9772.1 = 0 (STO de-selected and inactive – CU)
r9872.0 = r9872.1 = 0 (STO de-selected and inactive – MM)
r9773.0 = r9773.1 = 0 (STO de-selected and inactive – drive)
r9772.2 = r9872.2 = 0 (SS1 not requested – CU and MM)
1.
When terminals are grouped for "Safe Torque Off":
r9774.0 = r9774.1 = 0 (STO de-selected and inactive - group)
2. Run the drive
3. Ensure that the correct drive is running
4. Select SS1 when issuing the traversing command
Note:
The acceptance test must be carried out for each configured control, which may be via terminals, via the TM54F or via
PROFIsafe.
Check the following:
The drive is braked along the OFF3 ramp (p1135).
Before the SS1 delay time (p9652, p9852) expires, the following applies:
r9772.0 = r9772.1 = 0 (STO deselected and inactive - CU)
r9872.0 = r9872.1 = 0 (STO de-selected and inactive – MM)
5.
r9772.2 = r9872.2 = 1 (SS1 active – CU and MM)