Safety Integrated basic functions
9.1 General information
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
305
Password
The safety password protects the safety parameters against unauthorized write access.
In commissioning mode for Safety Integrated (p0010 = 95), you cannot change safety
parameters until you have entered the valid safety password in p9761 for the drives or
p10061 for the TM54F.
When Safety Integrated is commissioned for the first time, the following applies:
Safety password = 0
Default setting for p9761 = 0
In other words:
The safety password does not need to be set during initial commissioning.
In the case of a series commissioning of Safety or in the case of spare part installation,
the following applies:
The safety password is retained on the CF card and in the STARTER project.
No safety password is required in the case of spare part installation.
Change password for the drives
p0010 = 95 Commissioning mode
p9761 = Enter "old safety password".
p9762 = Enter "new password".
p9763 = Confirm "new password".
The new and confirmed safety password is valid immediately.
Change password for the TM54F
p0010 = 95 Commissioning mode
p10061 = Enter "Old TM54F Safety Password" (factory setting "0")
p10062 = Enter "new password"
p10063 = Acknowledge "new password"
The new and acknowledged safety password is valid immediately.
If you need to change safety parameters but you do not know the safety password, proceed
as follows:
1. Set the entire drive unit (Control Unit with all connected drives/components) to the factory
setting.
2. Recommission the drive unit and drives.
3. Recommission Safety Integrated.
Parameter overview for password (see SINAMICS S List Manual)
p9761 SI password input
p9762 SI password new
p9763 SI password acknowledgement
p10061 SI password input TM54F