Infeed
1.1 Active Infeed
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
29
Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.
This allows the attached drives to be braked in a controlled manner. Before the infeed is
switched off, the drives connected to the DC link should be in pulse inhibit mode.
Control and status messages
Table 1-2 Active Infeed open-loop control
Signal name Internal control word Binector input Display of internal
control word
PROFIdrive telegram
370
ON/OFF1 STWAE.0 p0840 ON/OFF1 r0898.0 A_STW1.0
OFF2 STWAE.1 p0844 1 OFF2 and
p0845 2 OFF2
r0898.1 A_STW1.1
Enable operation STWAE.3 p0852 Enable
operation
r0898.3 A_STW1.3
Disable motor
operation
STWAE.5 p3532 Disable motor
operation
r0898.5 A_STW1.5
Inhibit regenerating STWAE.6 p3533 Inhibit
regenerating
r0898.6 A_STW1.6
Acknowledge error STWAE.7 p2103 1 Acknowledge
or p2104
2 Acknowledge or
p2105 3 Acknowledge
r2138.7 A_STW1.7
Master ctrl by PLC STWAE.10 p0854 Master ctrl by
PLC
r0898.10 A_STW1.10
Table 1-3 Active Infeed status message
Signal name Internal status
word
Parameter PROFIdrive telegram 370
Ready to power up ZSWAE.0 r0899.0 A_ZSW1.0
Ready to run ZSWAE.1 r0899.1 A_ZSW1.1
Operation enabled ZSWAE.2 r0899.2 A_ZSW1.2
Fault active ZSWAE.3 r2139.3 A_ZSW1.3
No OFF2 active ZSWAE.4 r0899.4 A_ZSW1.4
Power-on disable ZSWAE.6 r0899.6 A_ZSW1.6
Alarm present ZSWAE.7 r2139.7 A_ZSW1.7
Master ctrl by PLC ZSWAE.9 r0899.9 A_ZSW1.9
Pre-charging completed ZSWAE.11 r0899.11 A_ZSW1.11
Line contactor energized feedback ZSWAE.12 r0899.12 A_ZSW1.12