Function modules
7.9 Basic positioner
Drive Functions
278 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
xx2x = ABS_POS -> p2648, p2651
xx3x = ABS_NEG -> p2648, p2652
Intermediate stop and canceling traversing block
The intermediate stop is activated by a 0 signal at p2640. After activation, the system brakes
with the parameterized deceleration value (p2620 or p2645).
The current traversing task can be canceled by a 0 signal at p2641. After activation, the
system brakes with the maximum deceleration (p2573).
The "intermediate stop" and "cancel traversing task" functions are only effective in the
modes "traversing blocks" and "direct setpoint input/MDI".
Function diagrams (see SINAMICS S List Manual)
3618 EPOS - direct setpoint input mode/MDI, dynamic values
3620 EPOS - direct setpoint input mode/MDI
Overview of key parameters (see SINAMICS S List Manual)
p2577 BI: EPOS modulo offset activation
p2642 CI: EPOS direct setpoint input/MDI, position setpoint
p2643 CI: EPOS direct setpoint input/MDI, velocity setpoint
p2644 CI: EPOS direct setpoint input/MDI, acceleration override
p2645 CI: EPOS direct setpoint input/MDI, delay override
p2648 BI: EPOS direct setpoint input/MDI, positioning type
p2649 BI: EPOS direct setpoint input/MDI, acceptance type
p2650 BI: EPOS direct setpoint input/MDI, setpoint acceptance edge
p2651 BI: EPOS direct setpoint input/MDI, positive direction selection
p2652 BI: EPOS direct setpoint input/MDI, negative direction selection
p2653 BI: EPOS direct setpoint input/MDI, setup selection
p2654 CI: EPOS direct setpoint input/MDI, mode adaptation
p2690 CO: EPOS position, fixed setpoint
p2691 CO: EPOS velocity, fixed setpoint
p2692 CO: EPOS acceleration override, fixed setpoint
p2693 CO: EPOS delay override, fixed setpoint