- Siemens Cordless Telephone User Manual

Function modules
7.3 Extended monitoring functions
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
225
7.3.2 Commissioning
The extended monitoring functions are activated while the commissioning Wizard is running.
Parameter r0108.17 indicates whether it has been activated.
7.3.3 Integration
The extended monitoring functions are integrated as follows in the system.
Function diagrams (see SINAMICS S List Manual)
8010 Speed messages
8013 Load monitoring
Overview of key parameters (see SINAMICS S List Manual)
Load monitoring
p2181[D] Load monitoring response
p2182[D] Load monitoring speed threshold 1
p2183[D] Load monitoring speed threshold 2
p2184[D] Load monitoring speed threshold 3
p2185[D] Load torque monitoring torque threshold 1 upper
...
p2190[D] Load torque monitoring torque threshold 3 lower
p2192[D] Load monitoring delay time
Speed setpoint monitoring
p2150[D] Hysteresis speed 3
p2151[C] CI: Speed setpoint
p2161[D] Speed threshold value 3
r2198.4 BO: ZSW monitoring 2, |n_setp| ≤ p2161
r2198.5 BO: ZSW monitoring 2, n_setp < 0