6.7 Automatic restart (vector, servo, infeed)
Drive Functions
188 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Overview of key parameters (see SINAMICS S List Manual)
r0069 Phase current, actual value
r0089 Actual phase voltage
p1820 Direction of rotation reversal of the output phases (vector)
p1821 Reversal of direction
p2507 LR absolute encoder adjustment status
6.7 Automatic restart (vector, servo, infeed)
Description
The automatic restart function is used to automatically restart the drive/drive group when the
power is restored after a power failure. In this case, all of the faults present are automatically
acknowledged and the drive is powered-up again. This function is not only restricted to line
supply faults; it can also be used to automatically acknowledge faults and to restart the
motor after any fault trips. In order to allow the drive to be powered-up while the motor shaft
is still rotating, the "flying restart" function should be activated using p1200.
CAUTION
Automatic restart functions in the vector, servo mode and for infeeds with closed-loop
infeed control. After the line supply voltage is connected, Smart Line Modules 5kW/10kW
automatically power themselves up.
WARNING
If p1210 is set to the value > 1, the Line Modules / motors can start automatically once the
line supply has been reestablished. This is especially critical, if, after longer line supply
failures, motors come to a standstill (zero speed) and it is incorrectly assumed that they
have been powered-down. For this reason, entering the area around the drive when it is in
this condition can cause death, serious injury, or considerable material damage.