6.3 Modular machine concept
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
183
Size Scaling parameter Default at initial commissioning
Reference temperature 100% = 100°C -
Reference electrical angle 100 % = 90° -
Overview of important parameters (refer to the List Manual)
p0340 Automatic calculation of motor/control parameters
p0573 Disable automatic calculation of reference values
p2000 Reference speed reference frequency
p2001 Reference voltage
p2002 Reference current
p2003 Reference torque
r2004 Reference power
p2005 Reference angle
p2007 Reference acceleration
6.3 Modular machine concept
Description
The modular machine concept is based on a maximum target topology created offline in
STARTER. The maximum design of a particular machine type is referred to as the maximum
configuration in which all the machine components that may be used are pre-configured in
the target topology. Sections of the maximum configuration can be removed by
deactivating/removing drive objects (p0105 = 2).
If a component fails, the sub-topology can also be used to allow a machine to continue
running until the spare part is available. In this case, however, no BICO sources must be
interconnected from this drive object to other drive objects.
Example of a sub-topology
The starting point is a machine created offline in STARTER for which "Drive 1" has not yet
been implemented.
Drive object "Drive 1" must be removed from the target topology via p0105 = 2 in offline
mode.
The DRIVE-CLiQ cable is reconnected from the Control Unit directly to "Drive 2".
Download the project by choosing "Load to drive object".
Copy from RAM to ROM.