Basic functions
6.2 Reference parameters/normalizations
Drive Functions
182 Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Scaling for servo object
Table 6-2 Scaling for servo object
Size Scaling parameter Default at initial commissioning
Reference speed 100 % = p2000 Induction motor p2000 = Maximum motor speed (p0322)
Synchronous motor p2000 = Rated motor speed (p0311)
Reference voltage 100 % = p2001 p2001 = 1000 V
Reference current 100 % = p2002 p2002 = Motor limit current (p0338); when p0338 = "0", 2
* rated motor current (p0305)
Reference torque 100 % = p2003 p2003 = p0338 * p0334; when "0", 2 * rated motor torque
(p0333)
Reference power 100 % = r2004 r2004 = p2003 * p2000 * π / 30
Reference angle 100% = p2005 90°
Reference acceleration 100% = p2007 0.01 1/s
2
Reference frequency 100 % = p2000/60 -
Reference modulation depth 100 % = Maximum output
voltage without overload
-
Reference flux 100 % = Rated motor flux -
Reference temperature 100% = 100°C -
Reference electrical angle 100 % = 90° -
Scaling for object A_Inf
Table 6-3 Scaling for object A_Inf
Size Scaling parameter Default at initial commissioning
Reference frequency 100 % = p2000 p2000 = p0211
Reference voltage 100 % = p2001 p2001 = r0206/r0207
Reference current 100 % = p2002 p2002 = p0207
Reference power 100 % = r2004 r2004 = p0206
Reference modulation depth 100 % = Maximum output
voltage without overload
-
Reference temperature 100% = 100°C -
Reference electrical angle 100 % = 90° -
Scaling for object B_Inf
Table 6-4 Scaling for object B_Inf
Size Scaling parameter Default at initial commissioning
Reference frequency 100 % = p2000 P2000 = 50
Reference voltage 100 % = p2001 p2001 = r0206/r0207
Reference current 100 % = p2002 p2002 = p0207
Reference power 100 % = r2004 r2004 = p0206